Air Change Rates

The amount of ventilation in an isolation room is usually expressed in Air Changes per Hour (ACH). By calculating the air change rate, the room ventilation can be compared to published standards, codes, and recommended guidelines. It can also be used to estimate the length of time required for removal of infectious particles.

One air change occurs in a room when a volume of air equal to the volume of the room is supplied or exhausted. The air change rate, called ACH, is the volume of air circulating every hour divided by the room volume.

The current JCAHO standard for negative pressure infectious isolation rooms is twelve (12) ACH minimum, with fifteen (15) ACH preferred. This air change rate may be different for other "critical areas" in the healthcare facility. See the table below. Beginning January 1, 2003, new construction or major renovation of "critical areas" are not grandfathered, and, must be brought up to the new standard.

Area Designation

Air Movement*

Minimum ACH

Exhaust to outdoors?

SURGERY AND CRITICAL CARE
Operating/Surgical Rooms

Out

15

Delivery Room

Out

15

Recovery Room

6

Critical and intensive care

6

Newborn intensive care

6

Treatment Room

6

Trauma Room

Out

15

Anesthesia gas storage

In

8

Yes

Endoscopy

In

6

Bronchoscopy

In

12

Yes

ER waiting rooms

In

12

Yes

Triage

In

12

Yes

Radiology waiting rooms

In

12

Yes

Special Procedure room

Out

15

NURSING
Patient room

6

Toilet room

In

10

Yes

Newborn Nursery Suite

6

Protective environment room

Out

12

Airborne infection isolation room

In

12

Yes

Isolation alcove or anteroom

In/Out

10

Yes

Labor/delivery/recovery

6

Labor/delivery/recovery/postpartum

6

Patient corridor

2

ANCILLARY
X-ray (surgical/critical care/catheterization

Out

15

X-ray (diagnostic & treatment)

6

Darkroom

In

10

Yes

Area Designation

Air Movement*

Minimum ACH

Exhaust to outdoors?

LABORATORY
General work areas

6

Biochemistry

Out

6

Cytology

In

6

Yes

Glass Washing

In

10

Yes

Histology

In

6

Yes

Microbiology

In

6

Yes

Nuclear Medicine

In

6

Yes

Pathology

In

6

Yes

Serology

Out

6

Sterilizing

In

10

Yes

Autopsy Room

In

12

Yes

Non-refrigerated body-holding room

In

10

Yes

Pharmacy

In

4

DIAGNOSTIC AND TREATMENT
Examination Room

6

Medication Room

Out

4

Treatment Room

6

Physical Therapy and Hydrotherapy

In

6

Soiled Workroom or Soiled Holding

In

10

Yes

Clean Workroom or Clean Holding

Out

4

* Air movement "Out" = positive pressure room, "In" = negative pressure room
No movement indication = Ambient (Neutral) pressure room